Optimal Configuration of Grid-Forming SVG Based on MRSCR

ZHAO Qingchun 1 , WANG Kun 1 , GE Jing 1 , ZHANG Haifeng 2a , SONG Xiaozhe 2b , ZHANG Yifu 2a    

  1. 1. Nanjing NARI-Relays Electric Company Limited, State Grid Electric Power Research Institute, Nanjing 211102, China; 2a. Electric Power Research Institute; 2b. Development Planning Department, State Grid Jilin Electric Power Company Limited, Changchun 130021, China
  • Received:2025-03-27 Online:2026-01-31 Published:2026-02-03

摘要: 针对大规模新能源机组并网运行存在诱发电力系统电压失稳风险问题, 虽然可以通过构网型 SVG( Static Var Generator)输出无功功率增强电网电压支撑能力, 但其优化配置方法仍需深入研究。 为此, 采用多新能源 场站短路比(MRSCR: Multiple New Energy Station Short Circuit Ratio)作为电压稳定评估指标, 建立电网电压支撑 强度量化分析模型, 重点揭示构网型 SVG 并网对 MRSCR 指标的提升机理。 基于电压稳定临界阈值约束, 构建 以装置容量最优化为目标的配置模型, 提出综合考虑电压稳定性和经济效益的构网型 SVG 多目标优化配置 方法。 仿真实验与算例对比结果表明, 所提配置方法可显著改善暂态过程中系统节点的电压支撑特性。

关键词: 构网型 SVG, 短路比, 系统电压强度, 优化配置

Abstract: With the accelerated promotion of China’s new energy power system, large-scale grid connected operation of new energy units will induce voltage instability risks in the power system. To address this technical challenge, a SVG( Static Var Generator) can be used to output reactive power to enhance the voltage support capability of the power grid. However, its optimization configuration method still needs further research. To solve this technical problem, the grid type SVG with autonomous voltage regulation capability enhances the voltage support capability of the power grid by outputting reactive power, but its optimization configuration method still needs further research. In response to this demand, the MRSCR( Multiple New Energy Station Short Circuit Ratio) is uesd as an indicator for assessing voltage stability and develops a quantitative model to analyze the voltage support capability of the power grid, and focuses on revealing the mechanism of the improvement of MRSCR index by grid connected SVG. Based on the constraint of voltage stability critical threshold, a configuration model with device capacity optimization as the objective is constructed, and a multi-objective optimization configuration method for grid type SVG considering voltage stability is proposed. The simulation results show that the proposed configuration method can significantly improve the voltage support characteristics of the system nodes in the transient process.

Key words: grid forming static var generator ( SVG ), short-circuit ratio, system voltage strength, optimize configuration